Evaluating the Contribution of Large Wind Power Plants on the Fault Current at the Lower Voltage Levels in Kenya

Eng. Erick Ohaga, CE, FIEK, AMCIArb, MKIM, MKOSSE,
KENYA POWER, P.O.BOX 26374-00100 Nairobi KENYA
*Corresponding author: eohaga@nuclear.co.ke

1 INTRODUCTION

The Feed in Tariff Policy has stimulated immense interest in the investment on renewable Energy sources in Kenya over the last 10 years. Each of The distributed generation and the Large Power plants introduced into the power system has an integral contribution on the system fault levels at the various bus-bars voltages. As the capacity of power systems is increasing, the short circuit current levels are continuously going up. The ratings of system switchgears and instrument transformers at many existing substations that were designed many years ago are now becoming underrated with present fault current levels. Such a situation is great concern to the protection engineers who strive to ensure that the security and dependability of the protection is not jeopardized. Besides risks of trivial CT saturation, which affects the security of the protection system, the major concern is on the effect on the rating of the existing system switchgears. In Kenya, the relationship between the system planning departments and system protection has not been symbiotic as is the case in other developed power system networks in developed countries. In view of this, a system study has been carried on impact of the 100MW wind-farm injecting at 220kV at Isinya 400kV/220kV substation in Kajiado County and suggest mitigating measures on the underlying impacts.

2 METHODOLOGY

The system was modeled using PSSE software. The system was simulated in the base year of 2020, 2025 and 2030 to check the levels of fault current at the various 66kV busbars. The selection of buses under study was based on the distance from the power plant (one near and one further apart).

Figure 1: Wind Power connection to Isinya Transmission substation.

2.1 Three Phase Fault Levels at 66kV bus-bar in 2020
The following results indicate the maximum three phase fault currents at the 66kV bus bars in the event of a fault in the year 2020.

2.2 Three Phase Fault Levels at 66kV bus-bar in 2025
The following results demonstrate the maximum three phase fault currents at the 66kV bus bars in the event of a fault in the year 2025.

2.3 Three Phase Fault Levels at 66kV bus-bar in 2030
The following results depict the maximum three phase fault currents at the 66kV bus bars in the event of a fault in the year 2030.

22.4 MITIGATING MEASURES
2.4.1 Current Limiting Reactor (CLR)
The CLR introduces higher impedance to the system by series–connected reactance in order to protect the equipment during fault condition. It reduces short circuit level to meet the system needs as well as stresses on busses, insulators, circuit breakers and other high voltage devices.

2.4.2 Fault Current Limiter (FCL)/BUS SPLITTING
Fault current limiter is very quickly capable of detecting and limiting a short circuit current by use of a small explosive charge to open a conductor. This diverts the current to a parallel fuse, which quenches the short circuit current.

3 RESULTS
The fault levels results indicate that at the lower voltages, the contribution of the large wind farm has a significant contribution on the short circuit current. Selecting one busbar near the power plant and another further from the plant.


4 CONCLUSION
It is evident that the contribution of large wind-farm on the system fault level is significant and mitigating measures should be provided by the developers at the approval stage, so that during the implementation, monitoring and evaluation is done to ensure compliance.

REFERENCES
[1] GE publication GET-3550F, Short Circuit Current Calculations, 1989.
[2] International Renewable Energy Agency, Renewable Energy Capacity Statistics 2015,
[3] IEC Short circuit currents in three-phase A.C. systems – Part 0: Calculation of currents, IEC Standard 60909-0, January 2016.
[4] IEC Short circuit currents – Calculation of effects – Part 2: Examples of calculation,
IEC Technical Report 60865-2, April 2015.
[5] Ontario Energy Board, Transmission System Code, August 2013.
[6] FiT application and applications Guidelines- Final copy 2015






  Author Profile
                                                           
   Eng. Erick Ohaga
Professional Engineer
                                      

















No comments:

Post a Comment